Serious Product Safety Report: Hania Bridal Henna Paste (2603-0118) Serious Product Safety Report: Water Gel Filler Beads for Vases sold via Desertcart (2603-0121) Serious Product Safety Report: TopBright Care Pets Dr Dog sold via Amazon (2603-0018) Serious Product Safety Report: EmdTOOL Cordless Drill sold via Amazon (2603-0013) Serious Product Safety Report: Feytory Rechargeable Wrench (2603-0012) Serious Product Safety Report: DayPlus Cordless Impact Wrench (2603-0010) Serious Product Safety Report: AIUNAOM Hair Dryer sold via Amazon (2603-0020) High Product Recall: Viessmann Vitorondens 200-T / 222-F Oil Condensing Boiler with Vitoflame 300 Oil Blue Flame Burner (2601-0285) Medium Product Safety Report: Kids Stuff Crazy Foaming Soap (2603-0273) Medium Product Recall: Tower Air Fryers (2503-0094)
High OPSS other

Product Recall: Viessmann Vitorondens 200-T / 222-F Oil Condensing Boiler with Vitoflame 300 Oil Blue Flame Burner (2601-0285)

Recall Date: 2026-03-10 Source: OPSS Reference: OPSS-PRODUCT-RECALL-VIESSMANN-VITORONDENS-200-T-SLASH-222-F-OIL-CONDENSING-BOILER-WITH-VITOFLAME-300-OIL-BLUE-FLAME-BURNER-2601-0285
🔍 View full details on GOV.UK (OPSS)
Official product safety report including images and corrective action

⚠ What You Should Do

Veissmann have notified end users who are affected by this issue and have warned installers of the risks.  

Affected users will receive a replacement ignition module and burner control unit, and a CO detector with shut-off function or conversion of the burner to current series configuration with pressure sensor.

Recall Details

Hazard

The product presents a high risk of asphyxiation as testing has indicated that some 2021-2023 boilers may ignite late, causing pressure damage and possible CO leaks. This could expose people in the building to unsafe exhaust gases and potentially lead to asphyxiation.

Corrective Action

Veissmann have notified end users who are affected by this issue and have warned installers of the risks.  

Affected users will receive a replacement ignition module and burner control unit, and a CO detector with shut-off function or conversion of the burner to current series configuration with pressure sensor.

Why This Product Is Dangerous

The product presents a high risk of asphyxiation as testing has indicated that some 2021-2023 boilers may ignite late, causing pressure damage and possible CO leaks. This could expose people in the building to unsafe exhaust gases and potentially lead to asphyxiation.